Fluke 1555C insulation tester for high voltage equipment testing / resistance measurement up to 1 TΩ
The FLUKE 1555C insulation tester is suitable for measuring voltages up to 10 kV, making it ideal for testing a wide variety of high voltage equipment including switches, motors, generators, and cables. The insulation tester meets CAT IV 600 V safety specifications, providing high safety for the user. The acquired data can be stored in internal memory or transferred to a PC via the interface. The large display allows for easy reading of values. This insulation tester is the ideal instrument for carrying out predictive or preventive maintenance, and is designed to identify potential equipment failures before they occur.
- Electrical safety category CAT III 1000 V and CAT IV 600 V
- The warning function alerts the user to the presence of voltage and provides the reading of the
voltage of up to 600 V AC or DC
- Selection of test voltages in steps of 50 V from 250 V to 1000 V, and
steps of 100 V above 1000 V
- The memory can store up to 99 measurements, and each one has a label
uniquely defined by the user for ease of use
- Long-lasting batteries allow for 750 tests per charge
- Automatic calculation of the Dielectric Absorption Ratio and the Polarization Index without
configuraciones adicionales
- The measurement system with guard eliminates the effect of surface leakage in very high measurements
resistencia
- Large digital/analog LCD display for easy viewing
- Ramp function for insulation breakdown tests
- Possibility to set the timer for up to 99 minutes for scheduled checks
- 3-year warranty
Electrical specifications
The accuracy of the tester has been specified for 1 year once calibrated at operating temperatures between 0 °C and 35 °C. For operating temperatures outside the range (from -20 °C to 0 °C and from 35 °C to 50 °C), add ±25% per °C, except in the bands with 20%, where you should add ±1% per °C.
Technical specifications
Test voltage (DC)
Rango
Accuracy (± reading)
250 V
< 200 kΩ
200 kΩ a 5 GΩ
5 GΩ a 50 GΩ
>50 GΩ
Not specified
5%
20%
Not specified
500 V
< 500 kΩ
500 kΩ a 10 GΩ
10 GΩ a 100 GΩ
>100 GΩ
Not specified
5%
20%
Not specified
1000 V
< 200 kΩ
200 kΩ a 20 GΩ
20 GΩ a 200 GΩ
>200 GΩ
Not specified
5%
20%
Not specified
2500 V
< 200 kΩ
200 kΩ a 50 GΩ
50 GΩ a 500 GΩ
>500 GΩ
Not specified
5%
20%
Not specified
5000 V
< 200 kΩ
200 kΩ a 100 GΩ
100 GΩ a 1 TΩ
>1 TΩ
Not specified
5%
20%
Not specified
Bar graph range
from -0 to 1 TΩ
Voltage accuracy in insulation testing
-0%, +10% at a load current of 1 mA
Rejection of AC current induced from the power grid
2 mA maximum
Charge speed for capacitive charging
5 seconds per μF
Download speed for capacity
1,5 s/μF
Leakage current measurement
Range: from 1 nA to 2 mA
Accuracy: ± (5% + 2 nA)
Capacity measurement
Range: from 0.01 nF to 15.00 μF
Accuracy: ± (15% rdg + 0,03 µF)
Temporizador
Range: from 0 to 99 minutes
Resolution: Adjustment: 1 minute, indication: 1 second
Warning of energized circuit
Warning range: from 30 to 660 V AC/DC, 50/60 Hz
Voltage accuracy: ± (15% + 2 V)
Software specifications
The basic FlukeView Forms™ software requires a PC with Windows XP, Windows Vista, Windows 7, or Windows 8
General technical specifications
Pantalla
75 x 105 mm
Power supply
12 V lead rechargeable battery, Yuasa NP2.8-12
Charger input (AC)
85 V a 250 V CA 50/60 Hz 20 VA
This class II instrument (with double insulation) is supplied with a class 1 power cable (with ground connection). The ground connection terminal (grounding pin) is not internally connected. This additional pin is solely for improving the retention of the plug.
Dimensions
269 x 277 x 160 mm
Peso
3,7 kg
Temperature (in operation).
From -20 °C to 50 °C (from -4 °F to 122 °F)
Temperatura (en almacenamiento)
From -20 °C to 65 °C (from -4 °F to 149 °F)
Humedad
From 80% to 31 ºC with linear decrease to 50% at 50 ºC
Altitud
2.000 m
Cabinet tightness
IP40
Input overload protection
1000 V CA
Electromagnetic compatibility
EN 61326
Safety compliance
IEC 61010-1: Overvoltage category II, pollution degree 2.
IEC 61010-2-030: Measurement of 600 V CAT II / 1000 V CAT III
IEC 61557-1, IEC 61557-2
Contents of the shipment
1 x Fluke 1555C insulation tester
1 x Test leads with alligator clips (red, black, green)
1 x Infrared adapter with interface cable
1 x CD-ROM with FlukeView Forms Basic
1 x AC power cable
1 x Flexible transport case
1 x User Manual on CD-ROM
1 x Quick reference card
1 x Software license agreement
1x Recording card
1 x FlukeView® Forms installation guide
1 x USB to IR cable installation guide
1 x High-performance crocodile clip cabless
More information:
Recommendation:
Metrological calibration certificate of:
Technical service and maintenance of:
Insulation meter
Insulation meter
International calibration certificate:
220 US$
Preventive maintenance and verification:
35 US$
Calibration certificate from EQUINLAB SAC calibration laboratory - Standard 17025
30 US$
Repair, corrective maintenance, adjustment, update, and validation:
60 US$
Includes:
** 2-year warranty.
** Discounts for the sale of two or more Insulation meter.
** Metrological calibration certificate for Insulation meter.
** Preventive maintenance, corrective (repair), technical service, and spare parts.
** Sales, maintenance, calibration, certification, and technical service 24 hours.
Envios a:Argentina, Bolivia, Brasil, Chile, Colombia, Costa, Rica, Cuba, Ecuador, El Salvador, Guatemala, Honduras, Mexico, Nicaragua, Panama, Paraguay, Peru, Puerto Rico, Dominican Republic, Uruguay, Venezuela.